Heatcraft / Bohn / Larkin Error Codes

What Heatcraft / Bohn / Larkin fault codes and alarms mean, and what a technician checks for each one. Need it fixed? We repair Heatcraft / Bohn / Larkin equipment across the Charlotte area.

Beacon II alarms

CodeMeaningWhat to check
A1High box temperatureAbove ALH for ALt time.
A2Low box temperatureBelow ALL for ALt time.
A3System start-up failureCompressor failed to start 4 times; retries after 4 min.
A4Input faultBox/suction temp or pressure transducer open/not installed.

Beacon II error indicator

CodeMeaningWhat to check
E1Room temperature sensor shorted/open/missingPumps down and stays off until cleared.
E2Defrost temperature sensor shorted/open/missingSystem keeps running.
E3Suction temperature sensor shorted/open/missingPumps down, stays off.
E4Suction pressure transducer shorted/open/missingPumps down, stays off.
E5Outdoor temperature sensor shorted/open/missingSystem keeps running.
E6Low superheatRetries after 4 min; alarm after 4th try.
E7Compressor shut down (HP/LP/oil switch open)Retries after 4 min; alarm after 4th try.
E9Multi-in / multi-out wiring errorNever connect OUT-OUT or IN-IN.