Heatcraft / Bohn / Larkin Error Codes
What Heatcraft / Bohn / Larkin fault codes and alarms mean, and what a technician checks for each one. Need it fixed? We repair Heatcraft / Bohn / Larkin equipment across the Charlotte area.
Beacon II alarms
| Code | Meaning | What to check |
|---|---|---|
| A1 | High box temperature | Above ALH for ALt time. |
| A2 | Low box temperature | Below ALL for ALt time. |
| A3 | System start-up failure | Compressor failed to start 4 times; retries after 4 min. |
| A4 | Input fault | Box/suction temp or pressure transducer open/not installed. |
Beacon II error indicator
| Code | Meaning | What to check |
|---|---|---|
| E1 | Room temperature sensor shorted/open/missing | Pumps down and stays off until cleared. |
| E2 | Defrost temperature sensor shorted/open/missing | System keeps running. |
| E3 | Suction temperature sensor shorted/open/missing | Pumps down, stays off. |
| E4 | Suction pressure transducer shorted/open/missing | Pumps down, stays off. |
| E5 | Outdoor temperature sensor shorted/open/missing | System keeps running. |
| E6 | Low superheat | Retries after 4 min; alarm after 4th try. |
| E7 | Compressor shut down (HP/LP/oil switch open) | Retries after 4 min; alarm after 4th try. |
| E9 | Multi-in / multi-out wiring error | Never connect OUT-OUT or IN-IN. |